Overview
In this section you will learn how to:
- Calculate voltages and currents in an unbalanced delta connected load supplied by a three-phase supply
- Calculate the current in the neutral wire of an unbalanced star connected load supplied by a three-phase four wire supply
- Calculate the potential difference between the load star point and the supply star point for an unbalanced star connected load supplied by a three-phase three wire supply
- Calculate voltages and currents in an unbalanced star connected load supplied by a three-phase four wire supply
- Calculate Active power in unbalanced three-phase loads
Three Phase Generator
Introduction
Unbalanced loads present a problem in that they can lead to poor performance because of larger current flow in some phases, unexpected neutral current flow, high harmonic content. Unbalanced motor and transformer loads can fail because of high vibration and overheating. So steps should always be taken to reduce electrical unbalance, by, for example, ensuring all electrical connections are good and windings are not damaged. Nonetheless, it is important to be able to calculate the effect of unbalance and this is more difficult than with balanced loads because the neutral voltage and/or current cannot be assumed to be zero.
When performing calculations on balanced three-phase circuits it is usual to work in terms of phase voltages and phase currents and carry out the calculation on one phase as for a single phase circuit. The solution for the other two phases is then found by taking into account the phase shift of 120° or -120°.
With unbalanced circuits, where, for example, the loads in the three phases are different, the above simplification is impossible, and it is necessary to determine the conditions in each phase separately by applying the laws of networks.
Unbalanced Delta Connected Load
Assuming the three-phase voltages to be balanced but with the load being different in each phase of the delta, the full line voltage will occur across each phase of the load. This is shown in Figure 1, with the accompanying phasor diagram in Figure 2.
Figure 1: Delta connected unbalanced load
© L.Gray UHI
Assuming the line voltages to be balanced then, taking the voltage VL1 as the reference phasor
The phase currents are then given by
N.B. the impedances must be expressed in complex cartesian (rectangular) or polar form.
The line currents are then determined from the phase currents in complex form by the following relationships:
Figure 2: Phasor diagram for an example of a Delta connected unbalanced load
© L.Gray UHI
The Active (P) power can be calculated by adding the power in each phase:
Total Active Power Ptotal = I2P1 R1 + I2P2 R2 + I2P3 R3 (Watts = W)
Example
Three impedances Z1, Z2, and Z3 are delta-connected to a symmetrical three-phase 400 V supply of phase sequence 123
Z1 = (10 + j0) ohms is connected between lines 1 and 2
Z2 = (8 + j6) ohms is connected between lines 2 and 3
Z3 = (5 - j5) ohms is connected between lines 3 and 1
Calculate the:
- Phase currents
- Line currents
- Total active power consumed.
- Draw the phasor diagram.
Solution
© L.Gray UHI
Let the line voltages be
VL1 = 400 〈0° V VL2 = 400 〈-120° V VL3 = 400 〈120° V
Z1 = (10 + j0 ) = 10 〈 0° Ω, Z2 = (8 + j6 ) = 10 〈 36.87°Ω, Z3 = (5 – j5 ) = 7.07 〈 -45° Ω
-
-
- Total Active Power P = I2P1 R1 + I2P2 R2 + I2P3 R3
-
= 402 x 10 + 402 x 8 + 56.62 x 5 = 16000 +12800 + 16018 W = 44.8 kW
Here is a circuit (using Multisim© 14.2) which confirms calculations are correct, allowing for rounding errors:
© L.Gray UHI
-
Phasor diagram
© L.Gray UHI
Self Assessment Questions
Now do the questions in the Self Assessment Questions folder for Week 5.
Effect of an Open-Circuited Phase
Suppose that due to a fault, one phase of the delta-connected load becomes open-circuited. This is shown in Figure 3 where the impedance Z1 is disconnected.
Figure 3: Delta connected unbalanced load, with phase 1 open circuited
© L.Gray UHI
The current IP1 now becomes zero
As before, IP2 = VL / Z2
IP3 = VL/ Z3
Also IL1 = IP1 – IP3 = - IP3
IL2 = IP2 – IP1 = IP2
IL3 = IP3 – IP2
Applying this to the previous example we have Figure 4:
Figure 4: Delta connected unbalanced load example, with phase 1 open-circuited
© L.Gray UHI
Using the previous calculations
IP1 = 0 IP2 = 40 〈 -156.87° IP3 = 56.6 〈 165°
IL1 = - IP3 = - 56.6 〈 165° A
IL2 = IP2 = 40 〈 -156.87° A
IL3 = I3 – I2 = 35.2〈120.57° (as before)
The total Active power now taken by the load is given by:
402 x 8 + 56.62 x 5 = 12800 +16018 W = 28.8 kW
Self Assessment Questions
Now do the questions in the Self Assessment Questions folder for Week 6.
Unbalanced Star Connected Load Supplied by a Three Phase Four Wire Supply
An unbalanced star-connected load may be connected to a three-phase supply by means of either a three-wire or a four-wire system. The four-wire system is the easiest to solve and is shown in Figure 5.
Figure 5: Four-wire System Star connected unbalanced load
Assuming that there is no impedance in the neutral (i.e. a short circuit), the voltages at the star point of the supply (o) and the load (o’) must be at the same potential, thus there is no voltage between points o and o’. The voltages across the loads in each phase are thus equal to the phase voltages of the supply.
Hence we have:
The neutral current is given by IN = IL1 + IL2 + IL3
If one phase becomes open-circuited with a four-wire system the current in that phase will become zero and the currents in the other two phases will remain unchanged.
Example of an Unbalanced 4-Wire Star Connected Load
Three impedances ZR = (4 + j3) ohms. ZY = (8 + j6) ohms and ZB = (6 + j4.5) ohms are star-connected across a four-wire 400 V supply
Determine:
- The current in each line
- The neutral current
- The Active power taken by the load
- Draw the phasor diagram
Solution
, ,
-
-
-
Total Active Power: P = I2L1 R1 +I2L2 R2 + I2L3 R3
= 46.22 x 4 + 23.12 x 8 + 30.82 x 6 = 8538 + 4269 + 5692 = 18.5 kW
Here is a circuit (using Multisim© 14.2) which confirms calculations are correct, allowing for rounding errors:
© L.Gray UHI
-
Phasor Diagram (not showing neutral current)
© L.Gray UHI
Self Assessment Questions
Now do the questions in the Self Assessment Questions folder for Weeks 7 and 8.
Unbalanced Star connected load supplied by a three phase three wire supply
The circuit for a three-wire system is shown in Figure 6. Here the star point of the load is not connected to the star point of the supply and there is thus no neutral connection. This means therefore that the two star points (O and O’) will not necessarily be at the same potential.
Figure 6: 3-wire System, Unbalanced Star connected load
© L.Gray UHI
In order to determine the current in each phase of the load it is first necessary to find the voltages across each of the loads. Equating the voltages around the loop ORO’O we have.
V1O = V1O’ + VO’O
V1O’ = V1O – VO’O
Now
IP1 = V1O’ /Z1 = V1O ‘Y1 = (V1O – VO’O) Y1 Remembering Y (admittance) = 1/Z
Similarly
IP2 = (V2O – VO’O) Y2
and
IP3 = (V3O – VO’O) Y3
Also the sum of the currents at o’ is zero therefore
IP1 + IP2 + IP3 = 0
And so
(V1O – VO’O)Y1 + (V2O – VO’O)Y2 + (V3O – VO’O) Y3= 0
V1O Y1 + V2OY2 + V3OY3 – VO’O (Y1 + Y2 + Y3) = 0
Then
V1O’ = V1O – VO’O
V2O’ = V2O – VO’O
V3O’ = V3O - VO’O
And
IP1 = IL1 =V1O’ / Z1
IP2 = IL2 = V2O’ / Z2
IP3 = IL3 = V3O’ / Z3
If one phase becomes open-circuited then the current in that phase will fall to zero. The currents in the other two phases will be equal in magnitude but opposite in sign and given by the line voltage divided by the sum of the impedances in those two phases. For example if Z1 becomes open-circuited then:
IP1 = IL1 = 0
IP2 = - IP3 = V23 / (Z2 + Z3) and of course, IL2 = IP2 and IL3 = IP3
Example
Loads of 2 ohms, (2 + j2) ohms and –j5 ohms are connected in star to the L1, L2 and L3 outputs of a three-phase 433-V, 50-Hz three-wire symmetrical system.
Determine
- The potential of the load star point with respect to the supply neutral
- The load phase voltages
- The line currents
- The Active power drawn by the load.
Solution
-
-
V1O’ = (VP1 – Vo’o) = 250 〈 0˚ - (-0.781 - j63.905) = 250.781 + j63.905 = 258.794 〈 14.295° V
V2O’ = (VP2 -VO’O) = 250 〈-120˚ - (-0.781 – j63.905) = -124.219 – j152.601 = 196.768 〈 -129.1° V
V3O, =(VP3 – VO’O) = 250 〈 120˚ - (-0.781 – j63.905) = -124.219 + j280.405 = 306.688 〈 113.9° V
-
IL1 = IP1 = V1O’ Y1 = 258.794 〈 14.295° x 0.5 = 129.397 〈 14.295° A
IL2 = IP2 =V2O’ Y2 = 196.772 〈 -129.1° x 0.354 〈 -45° = 69.657 〈 -174.1° A
IL3 = IP3 = V3O’ Y3 = 306.683 〈 113.89° x 0.2 〈 90° = 61.337 〈 203.89° A
-
Total Active Power P = I2P1 R1 + I2P2 R2 + I2P3 R3
= 129.3972 x 2 + 69.6572 x 2 + 61.3372 x 0 = 33487 + 9704 = 43.191 kW
Here is a circuit (using Multisim© 14.2) which confirms calculations are correct, allowing for rounding :
© L.Gray UHI
Self Assessment Questions
Now do the questions in the Self Assessment Questions folder for Weeks 9 and 10.
Conclusion
In this section you have learnt how to analyse systems with unbalanced loads. You have done this with Delta, 3-wire Star, and 4 wire Star connected unbalanced loads. You have also learnt how to calculate the Active power consumed by unbalanced loads. In the next section, Outcome 4, you will learn how this power can be measured using Wattmeters.